Our Products

Refrigerant No. R11 R12 R500 R502
Type of Refrigerant

Single

Single

Blend

Single

Chemical Structure

CCI3F

CCI2F2

R12/152a

R22/115

Molecular Weight (g/mol)

137.37

120.91

99.30

111.63

Boiling Point @ 14.7 psia(C)

23.71

-29.75

-33.5970~33.5969

-45.17~-44.94

Critical Temp (C)

197.96

111.97

102.09

80.15

Critical Pressure (psia)

639.27

599.89

604.56

568.2

Liquid Pressure @ 25 C(psia)

NA

NA

111.75

166.48

Vapor Pressure @ 25 C(psia)

NA

NA

111.42

166.45

O.D.P

1

1

0.74

0.33

G.W.P

4600

10600

7854

4516

Applications

1) Centrifugal Chillers

1) Medium to Low Temperature Refrigeration
2)Automobile Air-Conditioning

1) Commercial Refrigeration

1) Medium to Low Temperature Refrigeration

Color Representating

Orange (PMS#021)

White

Yellow(PMS#109)

Light Purple (Lavender) (PMS#251)

Refrigerant No. R22 R123 R124 R141b
Type of Refrigerant

Single

Single

Single

Single

Chemical Structure

CHClF2

CHCl2CF3

CHCIFCF3

CH3CCI2F

Molecular Weight (g/mol)

86.67

152.93

136.48

116.95

Boiling Point @ 14.7 psia(C)

-40.81

27.82

-11.96

32.05

Critical Temp (C)

96.15

183.68

122.28

206.81

Critical Pressure (psia)

723.74

531.1

525.66

646.87

Liquid Pressure @ 25 C(psia)

NA

NA

NA

NA

Vapor Pressure @ 25 C(psia)

NA

NA

NA

NA

O.D.P

0.055

0.02

0.022

0.11

G.W.P

1700

120

620

700

Applications

1) Medium to Low Temperature Refrigeration
2) Residential and Commercial Air-Conditioning

1) Centrifugal Chillers
2) Fire Fighting Agent

1) Special Applications
2) High Ambient Air-Conditioning

1) Solvent
2) Foaming Agent

Color Representating

Light Green (PMS#352)

Light Blue Grey (PMS#428)

Deep Green (Dot Green) (PMS#335)

Blue(ii)

LEGEND:

  • 1) O.D.P. is Ozone Depletion Potential values which are normalized indicator based on the value of 1.000 for CFC-11 from Montreal Protocol.
  • 2) G.W.P. is Global Warming Potential values which are relative to CO2 for integration period of 100 years from IPCC Third Assessment Report (2000).
  • 3) Refrigerant number is the standard designation based on those assigned by or recommended by AHRI-700 and ANSI/ASHARE Standard-34
  • 4) All data provided are for reference purposes and should be treated as estimates only.

NOTE:

  • (i) With respect to -40°C
  • (ii) Does not follow AHRI Refrigerant Color
  • (iii) These are indirect GWP values are from IPCC Fourth Assessment Report (2007)
  • (iv) If you need other packing, please check with our sales representatives or contact us via our Contact Page.
  • (v) Above listed products do not represent all the refrigerants available in the market. If you have a refrigerant not listed, pls contact our local sales representatives or drop us a message at the Contact Page.